LAKEAIR CIGAR LOUNGE CASE STUDY

How The Cigar Room Avoided a Costly DOAS Detour

The Cigar Room — Blaine, Minnesota

A project-specific air-purification and makeup-air strategy helped a new cigar lounge move forward without the roughly $80,000 additional cost of a proposed dedicated outdoor air system.

The Dream: A First-Class Cigar Lounge in Blaine

Jacob Hark set out to build The Cigar Room as a premium cigar-lounge experience in Blaine, Minnesota. The room had to feel intentional, not improvised: a place customers could enjoy, operators could manage, and the project team could confidently build.

Before construction decisions became permanent, Jacob brought LakeAir into the planning conversation. He shared the room information and renderings so the air-quality system could be considered as part of the lounge—not added later as an afterthought. That early decision gave the project a chance to begin with the room Jacob wanted to create.

Image of "The Cigar Room" in Blaine MN

The Original Plan: Eight Ducted LAAS-1600 Units

LakeAir’s original design did not begin with a DOAS. It centered on eight ducted LAAS-1600 smoke eaters, selected and distributed for the lounge itself. The aim was to capture and clean the smoking load where it was generated while preserving the look and function of a finished cigar lounge.

This was an integrated design conversation from the start. The system had to account for the room, expected use, duct paths, equipment placement, and the building’s existing mechanical capabilities. The question was never simply which machine to sell. It was how to build an air-quality strategy that fit Jacob’s project.

THE UNEXPECTED OBSTACLE

Then the Project Was Told It Needed an $80,000 DOAS

As the project moved forward, the contractor insisted that Jacob would need a dedicated outdoor air system, or DOAS. That conclusion introduced roughly $80,000 in additional ventilation-system cost and threatened the economics of the build-out.

For Jacob, the issue was no longer just equipment selection. The system that had been planned for his lounge was suddenly being treated as insufficient, and the path forward appeared to require a major new mechanical expense. Rather than accept that assumption at face value, LakeAir looked for the engineering basis behind it.

The Turning Point: Question the Assumption, Then Verify the Path

LakeAir’s position was that the contractor had not recognized the IMC 403.2 exception relevant to this project. In plain terms, that exception can allow an engineered air-cleaning and recirculation approach to reduce the outdoor makeup-air requirement when the project satisfies the applicable conditions. In a Teams meeting, Randolph Bush pushed for that exception to be considered rather than allowing the DOAS requirement to become an untested conclusion.

Randy then spoke directly with the local inspector about the proposed approach. The goal was not to bypass engineering, code review, or inspection. It was to determine whether the project could use a legitimate engineered solution that accounted for the building’s existing rooftop equipment and the eight-unit LakeAir smoke-control system.

Illustration of how the LakeAir LAAS ducted smoke eaters are designed to be deployed

THE RESOLUTION

An Engineered Plan That Let the Lounge Move Forward

The final approach was reviewed through the project’s mechanical-engineering and City of Blaine review process, then approved for the build-out. The eight ducted LAAS-1600 units remained the smoke-cleaning foundation of the design.

For makeup air, one of the building’s overhead rooftop units already had economizer capability. That existing RTU could serve the project’s makeup-air need. No ERV was required as part of the LakeAir equipment package. With each part assigned its proper job, the system became a practical whole: existing rooftop equipment for makeup air and distributed ducted LakeAir units for smoke purification.

Approximately $80,000 in avoided DOAS cost

By validating the engineered alternative instead of accepting the proposed DOAS path, Jacob was able to move forward with the lounge without that estimated additional ventilation-system expense.

Project at a Glance

Facility: The Cigar Room

Location: Blaine, Minnesota

Project type: New premium cigar lounge

Lounge area: Approximately 1,800 square feet

Ceiling height: 10 feet

Air-cleaning goal: 26 air changes per hour (ACH)

Original LakeAir design: Eight ducted LAAS-1600 units

Later obstacle: Proposed DOAS requirement

Makeup-air strategy: Existing overhead RTU with economizer capability

ERV required: No

Outcome: Approved engineered approach that avoided an estimated $80,000 DOAS cost path

The savings figure describes this project’s comparison between the proposed DOAS direction and the accepted LakeAir approach. It is project-specific, not a current LakeAir quotation.

What This Project Demonstrates

The Cigar Room was not a story about finding a shortcut. It was a story about asking the right question before an expensive assumption became permanent. Cigar-lounge planning works best when air purification, makeup air, existing HVAC capabilities, mechanical engineering, and municipal review are considered together.

  • Bring LakeAir into the project while the room is still being planned.
  • Design the smoke-control system for the actual lounge, not a generic rule of thumb.
  • Evaluate the existing HVAC equipment before assuming a new mechanical package is required.
  • Treat makeup air and smoke purification as coordinated parts of one system.
  • Bring the mechanical engineer and local review authority into the conversation early.

Start With the Lounge You Want to Build

If you are planning a cigar lounge, send LakeAir your floor plan, ceiling height, expected occupancy, and information on existing HVAC equipment. We will help you begin the air-quality conversation before an expensive assumption becomes a construction decision.